Atmos Leak Trial Manifold

Leak detection system for airport fuel hydrants

Atmos LTM Main

Leak trial manifold capable of accurate, low-flow measurement in hazardous areas to verify a tightness monitoring system on an airport fuel hydrant system.

  • Visual pressure readings via pressure gauge for diagnostic purposes.
  • Ergonomically designed based on industry standard (EI1584) coupler dimensions.
  • Ensures operators know how to respond to a real leak
  • Easily portable in a PELIā„¢ case

Technical specification

  • Covers segments up to 5000 m3 at 0.02l/h/m3 minimum detectable leak rate
  • Maximum Allowable Working Pressure: 25 Bar
  • Flow rate: 0.5 - 100 L/h
  • Weight: 34 kg All equipment contained within single PELI™ case
  • Inlet connection - 4 inches EI1584 coupler
  • Outlet - 1 m hose with ball valve and barb
  • Fine and course flow control valves
  • Meter accuracy +/- 0.5% of flow rate
  • Flow rate and cumulative display options
  • ATEX / IECEx approved flow meter
  • Panel mounted pressure gauge for diagnostics